Section 1The Guardian Series
Ten fixed frames share one platform: the same IE5 direct-drive EC fan array, Delta Controls package and 2 in. double-wall casing. Guardian CRAH frames are vertical units with V-bank coils, for downflow or upflow in the data hall, from 7,500–56,250 CFM. Guardian FA frames are horizontal blow-through units, with the filters, the fan array and then the coils, from 45,000–100,000 CFM.
Table 1.1 The frames
| Model | Series | Minimum CFM | Maximum CFM | Coil FPM at maximum | Coils | Fans | Dimensions | Shipping |
|---|---|---|---|---|---|---|---|---|
| GFA-CRAH-45 | Guardian CRAH | 2,400 | 7,500 | 625 | (1) C-36 | 1 | 61"W x 50"D x 102"H | One piece |
| GFA-CRAH-80 | Guardian CRAH | 4,000 | 12,500 | 625 | (1) C-60 | 2 | 85"W x 50"D x 102"H | One piece |
| GFA-CRAH-150 | Guardian CRAH | 8,000 | 25,000 | 625 | (2) C-60 | 2 | 85"W x 62"D x 120"H | One piece |
| GFA-CRAH-200 | Guardian CRAH | 11,200 | 33,000 | 589 | (2) C-84 | 3 | 109"W x 62"D x 120"H | One piece |
| GFA-CRAH-300 | Guardian CRAH | 18,000 | 56,250 | 625 | (2) C-120 | 4 | 145"W x 62"D x 120"H | One piece |
| GFA-FA-275 | Guardian FA | 18,000 | 45,000 | 500 | (2) C-120 | 4 | 140"W x 57"D x 128"H | One piece |
| GFA-FA-350 | Guardian FA | 21,600 | 55,000 | 509 | (2) C-144 | 6 | 164"W x 57"D x 128"H | One piece |
| GFA-FA-425 | Guardian FA | 21,600 | 66,000 | 611 | (2) C-144 | 8 | 162"W x 60"D x 152"H | One piece |
| GFA-FA-525 | Guardian FA | 32,400 | 82,000 | 506 | (3) C-144 | 9 | 162"W x 60"D x 194"H | Two pieces |
| GFA-FA-625 | Guardian FA | 32,400 | 100,000 | 617 | (3) C-144 | 9 | 162"W x 60"D x 226"H | Two pieces |
Maximum airflow is the lower of 625 FPM across the coil face and 500 FPM through the filters. Dimensions are width × depth × height.
Guardian CRAH configurations
D-xx downflow: return at the top (T), gallery side (G) or back side (R); discharge at the bottom (B), gallery side or back side. U-xx upflow: return at the bottom, gallery side or back side; discharge at the top, gallery side or back side. Nine combinations each. A side return adds a 30 in. return plenum and 30 in. to the unit height; a side discharge adds nothing.
Guardian FA configuration
H horizontal, end to end: return air inlet, filters, fan array, coils and supply air discharge, with a single-point chilled water manifold.
Figure 1.1 Air path, Guardian CRAH, downflow
A top return and bottom discharge, on the optional stand over a raised floor. Air is drawn through the filters and the V-bank coils by the fan array below them.
Figure 1.2 Air path, Guardian CRAH, upflow
A bottom return and top discharge. Air is drawn up through the filters and the V-bank coils by the fan array above them.
Figure 1.3 Air path, Guardian FA
Blow-through: the fan array pushes air through the coils to the discharge end.
Drain pans, dashed, are option D on every frame; the stand is option S.
Schematic, not to scale. Each frame's arrangement and dimensions are on its unit drawing (appendix A).
Model number
Every unit carries one complete model number of eleven segments, separated by hyphens. The options block is last and lists only the options furnished, in a fixed order; 0 means none.
| Segment | Values | Meaning |
|---|---|---|
| 1. Family | GFA | Guardian Series fan-array platform |
| 2. Series | CRAH or FA | CRAH: vertical V-bank. FA: horizontal blow-through. |
| 3. Frame | 45 to 625 | Frame size (nominal kW class): CRAH 45, 80, 150, 200 and 300; FA 275, 350, 425, 525 and 625 |
| 4. Airflow | D, U or H | D downflow, U upflow, H horizontal (FA only) |
| 5. Return and discharge | Two letters | The first letter is the return inlet, the second the supply discharge: T top, B bottom, G gallery side, R back side. A side return adds the 30 in. return plenum. Omitted for H. |
| 6. Coil | 6R or 8R | Coil rows |
| 7. Fluid | W or G30 | W water; G30 30% propylene glycol |
| 8. Piping | PT, PB or PS | Guardian CRAH: connection at the top, bottom or side (back side). Guardian FA: PT, through the roof |
| 9. Filter | M8 or M13 | MERV-8 standard; MERV-13 upgrade |
| 10. Volts | 460 | 460 V, 3-phase, 60 Hz |
| 11. Options | Letters, or 0 | The furnished options only, always in the fixed order T L P K Y E F A X S V; 0 means none. See the table below. |
Table 1.2 Options block, in fixed order
| Order | Letter | Option | Order | Letter | Option |
|---|---|---|---|---|---|
| 1 | T | Automatic transfer switch with dual power feed | 7 | E | Energy-metering PICV (EPIV) |
| 2 | L | Leak detection rope | 8 | F | Factory-installed valve package |
| 3 | D | Drain pans | 9 | A | Active front end (AFE) on each fan, IEEE-519 |
| 4 | P | Condensate pump (needs D) | 10 | X | Spare set of filters |
| 5 | K | Return air smoke detector | 11 | S | Adjustable equipment stand, 12–30 in. |
| 6 | Y | Strainer with blow-down | 12 | V | Vibration isolation pads at each leg |
Examples
| Unit as configured | Model number |
|---|---|
| GFA-CRAH-200: downflow, top return, bottom discharge, 6-row, water, top piping, MERV-8; ATS, leak rope and stand | GFA-CRAH-200-D-TB-6R-W-PT-M8-460-TLS |
| GFA-CRAH-300: downflow, back-side return (adds the 30 in. return plenum), gallery-side discharge, 8-row, 30% propylene glycol, side piping, MERV-13; AFE | GFA-CRAH-300-D-RG-8R-G30-PS-M13-460-A |
| GFA-CRAH-80: upflow, gallery-side return low (adds the 30 in. bottom return plenum), top discharge, 6-row, water, bottom piping; no options | GFA-CRAH-80-U-GT-6R-W-PB-M8-460-0 |
Section 2Selecting a unit
Each Guardian frame is a fixed design with a published airflow range. Selecting a unit means finding the smallest frame whose rating at your conditions meets the load, with the airflow inside that frame's range.
- Gather the design conditions.You need the net sensible load per unit in kW, the entering air dry bulb and wet bulb (or relative humidity), the entering and leaving water temperatures, the fluid, the airflow if the design fixes it, and the discharge arrangement.
- Choose the series.Guardian CRAH frames are vertical units with V-bank coils, for downflow or upflow, from 7,500–56,250 CFM at maximum airflow. Guardian FA frames are horizontal blow-through units, from 45,000–100,000 CFM.
- Find the frame in the capacity tables.Use the rating class closest to your conditions (table 2.1). Pick the smallest frame whose rating meets the load. Section 3 gives each frame's rating at its minimum, nominal and maximum airflow.
- Check the airflow against the frame's range.The airflow must sit between the frame's minimum and maximum (figure 2.1). Ratings with a coil face velocity above 457 FPM are above the coil's tested range and are marked est. (above tested range).
- Check the water conditions.The leaving water must be warmer than the entering water, the entering air warmer than the entering water, and the leaving water cooler than the entering air. A selection that breaks any of these is not rated.
- Choose 6-row or 8-row coils.6-row coils are standard. 8-row coils fit the same frame and add 8–9% sensible capacity at maximum airflow at class C3.
- Size the water flow.On water, the flow follows from the capacity and the water rise (below, and table 8.1). Glycol capacity and flow are rated per selection (section 8.5).
- Confirm the rating at your own conditions.Ask Cambridgeport (section 12) for a rating at your exact conditions. Certified coil and fan selections and electrical data come with the formal submittal.
Table 2.1 Rating classes
| Class | Entering air, dry bulb | Entering air, wet bulb | Entering water | Leaving water | Water rise |
|---|---|---|---|---|---|
| C1 | 75.0°F | 61.1°F | 45.0°F | 56.3°F | 11.3°F |
| C3 | 85.0°F | 62.5°F | 60.0°F | 75.0°F | 15.0°F |
| C5 | 97.0°F | 72.2°F | 70.0°F | 87.4°F | 17.3°F |
Airflow limits, every frame
Figure 2.1 Airflow range of each frame, CFM
Water flow on water
For example, the GFA-CRAH-200 at maximum airflow, 192 kW at the class C3 rise of 15.0°F, needs 88 GPM. Water pressure drop depends on the selection and comes with the certified coil selection.
Section 3Capacity
Net sensible capacity in kW on water, at each rating class's conditions (table 2.1). Nominal airflow is 80% of maximum. Water flow is at the class water rise.
Figure 3.1 Capacity range of each frame, kW
Net sensible capacity with 6-row coils at class C3 (85.0°F dry bulb and 62.5°F wet bulb entering air, 60.0°F entering and 75.0°F leaving water), from each frame's minimum to its maximum airflow (figure 2.1). 8-row coils add capacity at every airflow (section 2, step 6). Pick the smallest frame whose range covers the load, then read its rating in the tables below.
Table 3.1 Guardian CRAH, class C1
| Model | Coil | Minimum airflow | Nominal airflow | Maximum airflow | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| CFM | kW | Leaving air, °F | Water, GPM | CFM | kW | Leaving air, °F | Water, GPM | CFM | kW | Leaving air, °F | Water, GPM | |||||
| GFA-CRAH-451 C-36 coil, 1 fan | 6-row | 2,400 | 21 | 47.8 | 12 | 6,000 | 47 est. | 50.1 | 29 | 7,500 | 57 est. | 50.8 | 35 | |||
| 8-row | 2,400 | 22 | 46.5 | 13 | 6,000 | 51 est. | 48.1 | 31 | 7,500 | 62 est. | 48.7 | 38 | ||||
| GFA-CRAH-801 C-60 coil, 2 fans | 6-row | 4,000 | 34 | 47.8 | 21 | 10,000 | 79 est. | 50.1 | 48 | 12,500 | 96 est. | 50.8 | 58 | |||
| 8-row | 4,000 | 36 | 46.5 | 22 | 10,000 | 85 est. | 48.1 | 51 | 12,500 | 104 est. | 48.7 | 63 | ||||
| GFA-CRAH-1502 C-60 coils, 2 fans | 6-row | 8,000 | 69 | 47.8 | 42 | 20,000 | 158 est. | 50.1 | 95 | 25,000 | 191 est. | 50.8 | 115 | |||
| 8-row | 8,000 | 72 | 46.5 | 44 | 20,000 | 170 est. | 48.1 | 103 | 25,000 | 208 est. | 48.7 | 125 | ||||
| GFA-CRAH-2002 C-84 coils, 3 fans | 6-row | 11,200 | 96 | 47.8 | 58 | 26,400 | 210 est. | 49.9 | 127 | 33,000 | 255 est. | 50.6 | 154 | |||
| 8-row | 11,200 | 101 | 46.5 | 61 | 26,400 | 226 est. | 48.0 | 136 | 33,000 | 276 est. | 48.6 | 167 | ||||
| GFA-CRAH-3002 C-120 coils, 4 fans | 6-row | 18,000 | 155 | 47.8 | 93 | 45,000 | 355 est. | 50.1 | 215 | 56,250 | 430 est. | 50.8 | 260 | |||
| 8-row | 18,000 | 163 | 46.5 | 98 | 45,000 | 383 est. | 48.1 | 231 | 56,250 | 467 est. | 48.7 | 282 | ||||
Table 3.2 Guardian FA, class C1
| Model | Coil | Minimum airflow | Nominal airflow | Maximum airflow | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| CFM | kW | Leaving air, °F | Water, GPM | CFM | kW | Leaving air, °F | Water, GPM | CFM | kW | Leaving air, °F | Water, GPM | |||||
| GFA-FA-2752 C-120 coils, 4 fans | 6-row | 18,000 | 155 | 47.8 | 93 | 36,000 | 291 | 49.4 | 176 | 45,000 | 355 est. | 50.1 | 215 | |||
| 8-row | 18,000 | 163 | 46.5 | 98 | 36,000 | 312 | 47.6 | 188 | 45,000 | 383 est. | 48.1 | 231 | ||||
| GFA-FA-3502 C-144 coils, 6 fans | 6-row | 21,600 | 186 | 47.8 | 112 | 44,000 | 356 | 49.5 | 215 | 55,000 | 433 est. | 50.1 | 262 | |||
| 8-row | 21,600 | 195 | 46.5 | 118 | 44,000 | 381 | 47.7 | 230 | 55,000 | 467 est. | 48.2 | 282 | ||||
| GFA-FA-4252 C-144 coils, 8 fans | 6-row | 21,600 | 186 | 47.8 | 112 | 52,800 | 418 est. | 50.0 | 253 | 66,000 | 507 est. | 50.7 | 306 | |||
| 8-row | 21,600 | 195 | 46.5 | 118 | 52,800 | 450 est. | 48.1 | 272 | 66,000 | 550 est. | 48.7 | 332 | ||||
| GFA-FA-5253 C-144 coils, 9 fans | 6-row | 32,400 | 278 | 47.8 | 168 | 65,600 | 530 | 49.5 | 320 | 82,000 | 647 est. | 50.1 | 390 | |||
| 8-row | 32,400 | 293 | 46.5 | 177 | 65,600 | 568 | 47.6 | 343 | 82,000 | 697 est. | 48.1 | 421 | ||||
| GFA-FA-6253 C-144 coils, 9 fans | 6-row | 32,400 | 278 | 47.8 | 168 | 80,000 | 633 est. | 50.0 | 382 | 100,000 | 766 est. | 50.8 | 463 | |||
| 8-row | 32,400 | 293 | 46.5 | 177 | 80,000 | 682 est. | 48.1 | 412 | 100,000 | 832 est. | 48.7 | 503 | ||||
Class C1: 75.0°F dry bulb and 61.1°F wet bulb entering air, 45.0°F entering and 56.3°F leaving water.
Table 3.3 Guardian CRAH, class C3
| Model | Coil | Minimum airflow | Nominal airflow | Maximum airflow | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| CFM | kW | Leaving air, °F | Water, GPM | CFM | kW | Leaving air, °F | Water, GPM | CFM | kW | Leaving air, °F | Water, GPM | |||||
| GFA-CRAH-451 C-36 coil, 1 fan | 6-row | 2,400 | 16 | 63.8 | 7 | 6,000 | 36 est. | 66.0 | 16 | 7,500 | 43 est. | 66.8 | 20 | |||
| 8-row | 2,400 | 17 | 62.5 | 8 | 6,000 | 39 est. | 64.5 | 18 | 7,500 | 47 est. | 65.2 | 21 | ||||
| GFA-CRAH-801 C-60 coil, 2 fans | 6-row | 4,000 | 27 | 63.8 | 12 | 10,000 | 60 est. | 66.0 | 27 | 12,500 | 72 est. | 66.8 | 33 | |||
| 8-row | 4,000 | 28 | 62.5 | 13 | 10,000 | 65 est. | 64.5 | 30 | 12,500 | 78 est. | 65.2 | 36 | ||||
| GFA-CRAH-1502 C-60 coils, 2 fans | 6-row | 8,000 | 54 | 63.8 | 24 | 20,000 | 120 est. | 66.0 | 55 | 25,000 | 144 est. | 66.8 | 65 | |||
| 8-row | 8,000 | 57 | 62.5 | 26 | 20,000 | 130 est. | 64.5 | 59 | 25,000 | 157 est. | 65.2 | 71 | ||||
| GFA-CRAH-2002 C-84 coils, 3 fans | 6-row | 11,200 | 75 | 63.8 | 34 | 26,400 | 160 est. | 65.9 | 73 | 33,000 | 192 est. | 66.6 | 88 | |||
| 8-row | 11,200 | 80 | 62.5 | 36 | 26,400 | 173 est. | 64.3 | 79 | 33,000 | 209 est. | 65.0 | 95 | ||||
| GFA-CRAH-3002 C-120 coils, 4 fans | 6-row | 18,000 | 121 | 63.8 | 55 | 45,000 | 270 est. | 66.0 | 123 | 56,250 | 324 est. | 66.8 | 147 | |||
| 8-row | 18,000 | 128 | 62.5 | 58 | 45,000 | 292 est. | 64.5 | 133 | 56,250 | 353 est. | 65.2 | 160 | ||||
Table 3.4 Guardian FA, class C3
| Model | Coil | Minimum airflow | Nominal airflow | Maximum airflow | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| CFM | kW | Leaving air, °F | Water, GPM | CFM | kW | Leaving air, °F | Water, GPM | CFM | kW | Leaving air, °F | Water, GPM | |||||
| GFA-FA-2752 C-120 coils, 4 fans | 6-row | 18,000 | 121 | 63.8 | 55 | 36,000 | 223 | 65.4 | 102 | 45,000 | 270 est. | 66.0 | 123 | |||
| 8-row | 18,000 | 128 | 62.5 | 58 | 36,000 | 240 | 63.9 | 109 | 45,000 | 292 est. | 64.5 | 133 | ||||
| GFA-FA-3502 C-144 coils, 6 fans | 6-row | 21,600 | 145 | 63.8 | 66 | 44,000 | 272 | 65.5 | 124 | 55,000 | 329 est. | 66.1 | 150 | |||
| 8-row | 21,600 | 154 | 62.5 | 70 | 44,000 | 293 | 63.9 | 133 | 55,000 | 357 est. | 64.5 | 162 | ||||
| GFA-FA-4252 C-144 coils, 8 fans | 6-row | 21,600 | 145 | 63.8 | 66 | 52,800 | 318 est. | 66.0 | 145 | 66,000 | 382 est. | 66.7 | 174 | |||
| 8-row | 21,600 | 154 | 62.5 | 70 | 52,800 | 344 est. | 64.4 | 157 | 66,000 | 416 est. | 65.1 | 189 | ||||
| GFA-FA-5253 C-144 coils, 9 fans | 6-row | 32,400 | 217 | 63.8 | 99 | 65,600 | 406 | 65.4 | 185 | 82,000 | 491 est. | 66.1 | 224 | |||
| 8-row | 32,400 | 231 | 62.5 | 105 | 65,600 | 438 | 63.9 | 199 | 82,000 | 532 est. | 64.5 | 242 | ||||
| GFA-FA-6253 C-144 coils, 9 fans | 6-row | 32,400 | 217 | 63.8 | 99 | 80,000 | 481 est. | 66.0 | 219 | 100,000 | 577 est. | 66.8 | 263 | |||
| 8-row | 32,400 | 231 | 62.5 | 105 | 80,000 | 521 est. | 64.4 | 237 | 100,000 | 628 est. | 65.1 | 286 | ||||
Class C3: 85.0°F dry bulb and 62.5°F wet bulb entering air, 60.0°F entering and 75.0°F leaving water.
Table 3.5 Guardian CRAH, class C5
| Model | Coil | Minimum airflow | Nominal airflow | Maximum airflow | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| CFM | kW | Leaving air, °F | Water, GPM | CFM | kW | Leaving air, °F | Water, GPM | CFM | kW | Leaving air, °F | Water, GPM | |||||
| GFA-CRAH-451 C-36 coil, 1 fan | 6-row | 2,400 | 17 | 74.6 | 7 | 6,000 | 38 est. | 77.0 | 15 | 7,500 | 45 est. | 77.9 | 18 | |||
| 8-row | 2,400 | 18 | 73.2 | 7 | 6,000 | 41 est. | 75.4 | 16 | 7,500 | 49 est. | 76.2 | 19 | ||||
| GFA-CRAH-801 C-60 coil, 2 fans | 6-row | 4,000 | 28 | 74.6 | 11 | 10,000 | 63 est. | 77.0 | 25 | 12,500 | 76 est. | 77.9 | 30 | |||
| 8-row | 4,000 | 30 | 73.2 | 12 | 10,000 | 68 est. | 75.4 | 27 | 12,500 | 82 est. | 76.2 | 32 | ||||
| GFA-CRAH-1502 C-60 coils, 2 fans | 6-row | 8,000 | 57 | 74.6 | 22 | 20,000 | 126 est. | 77.0 | 50 | 25,000 | 151 est. | 77.9 | 60 | |||
| 8-row | 8,000 | 60 | 73.2 | 24 | 20,000 | 137 est. | 75.4 | 54 | 25,000 | 165 est. | 76.2 | 65 | ||||
| GFA-CRAH-2002 C-84 coils, 3 fans | 6-row | 11,200 | 79 | 74.6 | 31 | 26,400 | 168 est. | 76.8 | 66 | 33,000 | 202 est. | 77.6 | 80 | |||
| 8-row | 11,200 | 84 | 73.2 | 33 | 26,400 | 182 est. | 75.2 | 72 | 33,000 | 220 est. | 76.0 | 86 | ||||
| GFA-CRAH-3002 C-120 coils, 4 fans | 6-row | 18,000 | 128 | 74.6 | 50 | 45,000 | 284 est. | 77.0 | 112 | 56,250 | 340 est. | 77.9 | 134 | |||
| 8-row | 18,000 | 136 | 73.2 | 53 | 45,000 | 308 est. | 75.4 | 121 | 56,250 | 370 est. | 76.2 | 146 | ||||
Table 3.6 Guardian FA, class C5
| Model | Coil | Minimum airflow | Nominal airflow | Maximum airflow | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| CFM | kW | Leaving air, °F | Water, GPM | CFM | kW | Leaving air, °F | Water, GPM | CFM | kW | Leaving air, °F | Water, GPM | |||||
| GFA-FA-2752 C-120 coils, 4 fans | 6-row | 18,000 | 128 | 74.6 | 50 | 36,000 | 235 | 76.4 | 92 | 45,000 | 284 est. | 77.0 | 112 | |||
| 8-row | 18,000 | 136 | 73.2 | 53 | 36,000 | 253 | 74.8 | 100 | 45,000 | 308 est. | 75.4 | 121 | ||||
| GFA-FA-3502 C-144 coils, 6 fans | 6-row | 21,600 | 153 | 74.6 | 60 | 44,000 | 287 | 76.4 | 113 | 55,000 | 346 est. | 77.1 | 136 | |||
| 8-row | 21,600 | 163 | 73.2 | 64 | 44,000 | 309 | 74.8 | 122 | 55,000 | 375 est. | 75.5 | 147 | ||||
| GFA-FA-4252 C-144 coils, 8 fans | 6-row | 21,600 | 153 | 74.6 | 60 | 52,800 | 335 est. | 77.0 | 132 | 66,000 | 401 est. | 77.8 | 158 | |||
| 8-row | 21,600 | 163 | 73.2 | 64 | 52,800 | 362 est. | 75.3 | 142 | 66,000 | 436 est. | 76.1 | 172 | ||||
| GFA-FA-5253 C-144 coils, 9 fans | 6-row | 32,400 | 230 | 74.6 | 90 | 65,600 | 428 | 76.4 | 168 | 82,000 | 517 est. | 77.1 | 203 | |||
| 8-row | 32,400 | 244 | 73.2 | 96 | 65,600 | 461 | 74.8 | 181 | 82,000 | 560 est. | 75.4 | 220 | ||||
| GFA-FA-6253 C-144 coils, 9 fans | 6-row | 32,400 | 230 | 74.6 | 90 | 80,000 | 507 est. | 77.0 | 199 | 100,000 | 607 est. | 77.8 | 239 | |||
| 8-row | 32,400 | 244 | 73.2 | 96 | 80,000 | 548 est. | 75.4 | 216 | 100,000 | 660 est. | 76.2 | 259 | ||||
Class C5: 97.0°F dry bulb and 72.2°F wet bulb entering air, 70.0°F entering and 87.4°F leaving water.
Section 4Capacity against entering water
Net sensible capacity of each frame at nominal airflow with 6-row coils, 85.0°F entering air (class C3's dry bulb, 62.5°F wet bulb) and the class C3 water rise of 15.0°F, across entering water from 45°F to 65°F. The leaving air rises with the entering water, so capacity falls as the water warms.
Figure 4.1 Guardian CRAH
Figure 4.2 Guardian FA
Section 3 gives the capacities at the rating classes' conditions, with leaving air and water flow.
Section 5Physical data and construction
Table 5.1 Physical data
| Model | Dimensions | Coils, finned face | Coil face area, ft² | Fans | Fan size, mm | Filters | Shipping | Operating weight |
|---|---|---|---|---|---|---|---|---|
| GFA-CRAH-45 | 61"W x 50"D x 102"H | 1 C-36, 48 × 36 in. | 12 | 1 | 560 | 8 | One piece | 1,503 lb est. |
| GFA-CRAH-80 | 85"W x 50"D x 102"H | 1 C-60, 48 × 60 in. | 20 | 2 | 560 | 12 | One piece | 1,888 lb est. |
| GFA-CRAH-150 | 85"W x 62"D x 120"H | 2 C-60, 48 × 60 in. | 40 | 2 | 560 | 18 | One piece | 2,575 lb est. |
| GFA-CRAH-200 | 109"W x 62"D x 120"H | 2 C-84, 48 × 84 in. | 56 | 3 | 560 | 24 | One piece | 3,060 lb est. |
| GFA-CRAH-300 | 145"W x 62"D x 120"H | 2 C-120, 54 × 120 in. | 90 | 4 | 560 | 36 | One piece | 3,705 lb est. |
| GFA-FA-275 | 140"W x 57"D x 128"H | 2 C-120, 54 × 120 in. | 90 | 4 | 710 | 25 | One piece | 4,342 lb est. |
| GFA-FA-350 | 164"W x 57"D x 128"H | 2 C-144, 54 × 144 in. | 108 | 6 | 710 | 30 | One piece | 5,087 lb est. |
| GFA-FA-425 | 162"W x 60"D x 152"H | 2 C-144, 54 × 144 in. | 108 | 8 | 710 | 36 | One piece | 6,021 lb est. |
| GFA-FA-525 | 162"W x 60"D x 194"H | 3 C-144, 54 × 144 in. | 162 | 9 | 710 | 48 | Two pieces | 7,568 lb est. |
| GFA-FA-625 | 162"W x 60"D x 226"H | 3 C-144, 54 × 144 in. | 162 | 9 | 710 | 54 | Two pieces | 8,126 lb est. |
Dimensions are width × depth × height. A side return on a Guardian CRAH frame adds 30 in. to the height. Two-piece frames ship as sections: GFA-FA-525, 64 in. and 130 in. high; GFA-FA-625, 74 in. and 152 in. high. Weights are estimates; the unit drawing and the submittal carry the certified weights and the rigging points.
Figure 5.1 The frames to scale, width and height
Every frame at one scale, with a 6 ft person for reference; the grid is at 2 ft. Each outline is the unit's width by height, without the Guardian CRAH's stand or a side return plenum.
Table 5.2 Construction
| Element | Construction |
|---|---|
| Casing | Galvanized steel, an 18GA outer skin, powder coated, and a 14GA inner skin, on both series. 2 in. double wall, R-14, with no exposed insulation in the airstream. |
| Factory tests | Options: a casing leakage test at 1.5 times the design total static pressure, and a factory run and airflow test, each before shipment. The controls are tested point to point on every unit. |
| Base and floor | 16GA floor on a 4 in. 12GA galvanized base frame. An adjustable stand for Guardian CRAH frames, 12 to 30 in., is option S, shipped loose. |
| Coils | Chilled water coils, 6-row standard, 8-row optional, in the same frame. Guardian CRAH coils form a V-bank. |
| Fan array | IE5 direct-drive EC fans: 560 mm on Guardian CRAH, 710 mm on Guardian FA. No belts and no lubrication points; each fan withdraws on its own. |
| Filters | MERV-8, side-loading V-bank on Guardian CRAH and front-loading at the inlet face on Guardian FA; MERV-13 is an upgrade. |
| Drain pans | Option D: 18GA stainless steel, one per coil, under each coil on Guardian CRAH and downstream of each coil on Guardian FA, each with a gravity drain. A condensate pump (option P) needs them. |
| Panels | Separate motor power and control panels, each with its own door, built into the unit. |
| Power | 460 V, 3-phase, 60 Hz, single point. |
Standard on every unit
- Base piping package: coil headers, isolation valves, air vents and P/T ports, with pressure-independent control valves (PICV) shipped loose for field installation
- Single-point chilled water connection, grooved or flanged
- Delta Controls DDC package with a 4.3 in. touchscreen, factory programmed and point-to-point tested; BACnet/IP native
- IE5 direct-drive EC fan array
- 2 in. double-wall insulated casing, R-14
- MERV-8 filters
- Return air temperature, supply air temperature and supply air humidity sensors, factory mounted
- 460 V, 3-phase, 60 Hz single-point power
Section 6Electrical data
Every unit takes 460 V, 3-phase, 60 Hz power at a single point, to the motor power panel. An automatic transfer switch with a dual power feed is an option on every frame (option T).
Table 6.1 Electrical data
| Model | Fans | Fan motor, HP | Full load amps | Minimum circuit ampacity | Maximum overcurrent protection |
|---|---|---|---|---|---|
| GFA-CRAH-45 | 1 | 5 | 8 A est. | 9.5 A est. | 15 A est. |
| GFA-CRAH-80 | 2 | 5 | 14 A est. | 15.5 A est. | 20 A est. |
| GFA-CRAH-150 | 2 | 7.5 | 20 A est. | 22.3 A est. | 30 A est. |
| GFA-CRAH-200 | 3 | 7.5 | 29 A est. | 31.3 A est. | 40 A est. |
| GFA-CRAH-300 | 4 | 7.5 | 38 A est. | 40.3 A est. | 45 A est. |
| GFA-FA-275 | 4 | 10 | 50 A est. | 53 A est. | 60 A est. |
| GFA-FA-350 | 6 | 10 | 74 A est. | 77 A est. | 80 A est. |
| GFA-FA-425 | 8 | 10 | 98 A est. | 101 A est. | 110 A est. |
| GFA-FA-525 | 9 | 10 | 110 A est. | 113 A est. | 125 A est. |
| GFA-FA-625 | 9 | 10 | 110 A est. | 113 A est. | 125 A est. |
Electrical figures are estimates. Certified electrical data comes with each unit's fan selection and the formal submittal; the nameplate carries the minimum circuit ampacity and maximum overcurrent protection.
Power quality
With the active front end option (option A) on each fan, the unit's current distortion is under 1% and its power factor 0.98 at the connection, so the fan load needs no external harmonic filters, oversized neutrals or transformer derating (IEEE-519). With the ATS and active front end options together, the fan array rides through a transfer.
Field connections
- Power: one feeder to the motor power panel, sized and protected to the nameplate.
- Building automation: BACnet/IP at the control panel, with dual Ethernet ports.
- Fans: a factory-wired Modbus RS-485 trunk from the controller to every fan.
Section 7Planning, rigging and clearances
Every frame separates mechanical service from electrical and controls service, so the two never need the same clearance. Each assembly withdraws on its own, horizontally, so one component can be serviced while the rest stay in place.
Table 7.1 Where service happens
| Component | Guardian CRAH | Guardian FA |
|---|---|---|
| Coils | Front (gallery) | Discharge end |
| Fans | Front (gallery) | Inlet end |
| Filters | Side (side-loading V-bank) | Inlet end (front-loading, full face) |
| Control and power panels | Side | Side |
Table 7.2 Service clearances, Guardian CRAH
| Model | Front gallery (coils and fans) | Side (panels and filters) | Opposite side | Rear |
|---|---|---|---|---|
| GFA-CRAH-45 | 48 in. | 36 in. | 12 in. | 24 in. |
| GFA-CRAH-80 | 48 in. | 36 in. | 12 in. | 24 in. |
| GFA-CRAH-150 | 60 in. | 36 in. | 12 in. | 24 in. |
| GFA-CRAH-200 | 60 in. | 36 in. | 12 in. | 24 in. |
| GFA-CRAH-300 | 60 in. | 36 in. | 12 in. | 24 in. |
Table 7.3 Service clearances, Guardian FA
| Model | Inlet end (filters and fans) | Discharge end (coils) | Panel side | Opposite end | Top |
|---|---|---|---|---|---|
| GFA-FA-275 | 48 in. | 48 in. | 24 in. | None | None |
| GFA-FA-350 | 48 in. | 48 in. | 24 in. | None | None |
| GFA-FA-425 | 48 in. | 48 in. | 36 in. | None | None |
| GFA-FA-525 | 48 in. | 48 in. | 36 in. | None | None |
| GFA-FA-625 | 48 in. | 48 in. | 36 in. | None | None |
Each unit drawing depicts its clearances (appendix A). Where the National Electrical Code (NEC 110.26) sets a larger working space at the panel face, provide the larger.
Figure 7.1 Clearances in plan, GFA-CRAH-200
Figure 7.2 Clearances in plan, GFA-FA-425
To scale, from above, as each unit drawing's top view; clearances are shaded. Guardian CRAH: coils and fans withdraw into the front gallery; panels and filters are serviced from the side. Guardian FA: filters and fans at the inlet end, coils at the discharge end; air enters at the inlet (red) and leaves at the discharge (blue). Tables 7.2 and 7.3 give every frame's clearances.
Planning the room
- Plan the service faces at layout. Withdrawal needs the clearance on the drawing plus room for the technician and a lift or transfer cart, and it can't be recovered once the units are set.
- A side return on a Guardian CRAH frame adds the 30 in. return plenum to the unit height; check the overhead clearance.
- Downflow units need an unobstructed raised-floor plenum. Check the floor grille free area against the unit airflow, and coordinate the stand height with the floor depth.
- Check the structure against the unit's operating weight (table 5.1, an estimate until the submittal).
- Set each unit level within 1/8 in. over its footprint, shimmed at the base rail.
- On units with drain pans (option D), pipe the condensate drain full size with a trap at least 1 in. deep per 1 in. w.g. of the unit's negative static pressure, plus 1 in., pitched at least 1/8 in. per foot.
Rigging and shipping
Rig at the lift points on the unit drawing, by forklift from below with the skid intact or by a spreader-bar lift. Never lift by the piping, coil headers or panel flanges, and keep the unit upright. The GFA-FA-525 and GFA-FA-625 ship in two pieces; each section is rigged on its own and the sections are joined on site with the factory gasket kit. Check door openings, elevators and the rigging path against the shipping dimensions before release.
Section 8Piping and water
8.1 Guardian CRAH piping
- Factory supply and return headers, with isolation valves on each coil, to a single-point supply and return connection at the top, bottom or side, grooved; its size is on the unit drawing.
- A PICV on each coil, with a modulating fail-safe actuator, shipped loose for field installation.
- Vent, drain and P/T ports on each coil.
8.2 Guardian FA piping
- A factory-piped manifold with one supply and one return field connection, through the roof, 150# flange or grooved coupling.
- A53 headers with shop-welded branches flanged at every coil, supported on the frame with no load on the coil connections.
- A PICV on each header, shipped loose for field installation; vents, drains and P/T ports on the headers.
Figure 8.1 Guardian CRAH piping, front
- V-bank coils (a two-coil frame)
- PICV and actuator on each coil's return, shipped loose
- Isolation valves on each coil, factory installed
- Supply and return headers, factory piped
- Option: strainer with blow-down
- Single-point supply and return connection at the top, bottom or side, grooved; size on the unit drawing
Each coil is piped to the headers, with vent, drain and P/T ports.
Figure 8.2 Guardian FA piping, discharge end
- Coils, stacked (two or three by frame)
- Branches flanged at every coil
- Supply header, A53
- Return header, A53
- A single field connection on each header, through the roof, 150# flange or grooved coupling, with a PICV shipped loose
Headers supported on the frame, with vents, drains and P/T ports.
Schematic, not to scale; supply blue, return red. Valve positions for each project are on the submittal's piping detail.
8.3 Control valves
Pressure-independent control valves (PICV) come with every unit, selected against the coil's design flow and installed in the field in the positions on the piping detail. Energy-metering valves (EPIV, option E) and a factory-installed valve package (option F) are options. A strainer with blow-down is option Y; otherwise install a strainer of 20 mesh or finer in the supply, upstream of the unit.
8.4 Field piping
- Flush and clean the building loop with the unit isolated before connecting it. Construction debris is the leading cause of fouled coils and failed control valves in the first year.
- Support field piping on its own, with no strain on the unit connections.
- Treat the loop to the project's water-treatment specification and keep it closed.
- Balance to the scheduled flow at the P/T ports and set each PICV to its design flow.
Table 8.1 Water flow by water rise
| Water rise | GPM per kW | GPM per ton |
|---|---|---|
| 10°F | 0.68 | 2.40 |
| 12°F | 0.57 | 2.00 |
| 14°F | 0.49 | 1.71 |
| 15°F | 0.45 | 1.60 |
| 16°F | 0.43 | 1.50 |
| 18°F | 0.38 | 1.33 |
| 20°F | 0.34 | 1.20 |
On water. Water pressure drop depends on the selection and comes with the certified coil selection; carry it in the plant's pump head.
8.5 Glycol
Units run on water or propylene glycol; the model number's fluid segment is W for water and G30 for 30% propylene glycol. Glycol reduces capacity and changes the flow and pressure drop, so glycol capacity and flow are rated per selection: ask Cambridgeport for a rating at your concentration and conditions. Check the delivered glycol type and concentration by refractometer at fill and record them.
8.6 Condensation
Units run dry when the entering water is above the room's dew point. Drain pans are option D on every frame: stainless steel, one per coil, under each coil on Guardian CRAH and downstream of each coil on Guardian FA, each with a gravity drain, for commissioning, dehumidification excursions and coil cleaning; a condensate pump is option P, with the drain pans. Without drain pans, keep the entering water above the room's dew point.
Section 9Controls
9.1 The controls package
A Delta Controls DDC controller with I/O expansion and a 4.3 in. touchscreen on the control panel door, factory programmed and point-to-point tested. BACnet/IP native, with dual Ethernet ports, to the building automation system, and a Modbus RS-485 trunk to every fan. The control panel is NEMA 4, with a 24 VDC supply, fused 24 VAC and two-level terminals; the power panel has a fused busbar, a 15 A class CC fuse for each fan and a disconnect.
Figure 9.1 Controls and network
Schematic. The supply fan fault comes through the Modbus trunk or a hardwired input. Options are dashed.
Figure 9.2 Power distribution
One-line, schematic: four fans shown; each frame's fan count is in table 6.1. Options are dashed.
Table 9.1 Points
| Point | Type | End device | Included |
|---|---|---|---|
| Supply air temperature (TE-01) | Analog input | Duct temperature sensor, 4–20 mA | Standard |
| Return air temperature (TE-02) | Analog input | Duct temperature sensor, 4–20 mA | Standard |
| Supply air humidity (UE-01) | Analog input | Duct humidity and temperature sensor, 4–20 mA | Standard |
| Filter differential pressure (DPT-01) | Analog input | Differential pressure transmitter, −0.4 to 10 in. w.g., auto-zero | Standard |
| Cooling coil valve feedback (TVF-01) | Analog input | PICV with a modulating fail-safe actuator | Standard |
| Cooling coil valve control (TV-01) | Analog output | To the PICV actuator, 2–10 V | Standard |
| Supply fan speed control (SPD-01) | Analog output | To the EC fan array | Standard |
| Supply fan start command (RE-01) | Digital output | Fan array enable relay | Standard |
| Supply fan fault | Digital input | Through the Modbus trunk or a hardwired input | Standard |
| Water leak alarm (LD-01) | Digital input | Leak detection rope, 65 ft, auto reset | Option L |
| ATS common alarm | Digital input | ATS auxiliary contact | Option T |
The project's sequences of operation, network architecture and full points list come with the submittal.
Table 9.2 Standard sequences
| Function | Standard behavior |
|---|---|
| Temperature control | The PICV modulates to hold the supply air (or return air, per project) setpoint; the fan array modulates to hold the airflow or static pressure setpoint. |
| Fan management | N+1 fan logic: each fan's health is monitored, the array rebalances when a fan is lost, and the building automation system gets an alarm. |
| Teamwork | Units on a common header coordinate staged capacity, rotate the lead unit and share a setpoint. |
| Leak detection | Under-unit sensing raises an alarm and, per project, closes the chilled water valve. |
| Loss of airflow and freeze protection | Proof of flow and low-limit protection per the sequence; automatic restart per the project setting. |
| Power transfer | With the ATS and active front end options, the fan array rides through a transfer without dropping out. |
Section 10Options
Most options are chosen in the model number. Those in the options block print as letters, in the fixed order below; others are choices in the model number's other segments. The factory tests are ordered with the unit and listed on its documents, but have no letter.
Table 10.1 Options block
| Letter | Option |
|---|---|
| T | Automatic transfer switch with dual power feed |
| L | Leak detection rope |
| D | Drain pans |
| P | Condensate pump (needs D) |
| K | Return air smoke detector |
| Y | Strainer with blow-down |
| E | Energy-metering PICV (EPIV) |
| F | Factory-installed valve package |
| A | Active front end (AFE) on each fan, IEEE-519 |
| X | Spare set of filters |
| S | Adjustable equipment stand, 12–30 in. |
| V | Vibration isolation pads at each leg |
Table 10.2 Choices in other segments
| Code | Choice |
|---|---|
| 8R | 8-row coils, in the same frame (coil segment) |
| G30 | 30% propylene glycol (fluid segment) |
| M13 | MERV-13 filters (filter segment) |
| PT, PB, PS | Piping connection at the top, bottom or side (piping segment) |
Table 10.3 Options not in the model number
| Option | What it is |
|---|---|
| Casing leakage test | The casing proof-tested for leakage at 1.5 times the design total static pressure before shipment |
| Factory run and airflow test | The unit run at the factory, with its airflow measured, before shipment |
Non-standard stand heights and seismic anchorage are engineered per project.
Section 11Application notes
| Topic | Guidance |
|---|---|
| Humidification and reheat | Guardian units cool sensibly and carry no humidifier or reheat coil. Data halls usually hold the dew point at the plant or with dedicated units, and a sensible-only unit is simpler and lighter. Where a schedule requires humidification or reheat on the unit, the Custom CRAH line provides it. |
| Altitude | Ratings are at sea-level standard air. Above about 2,500 ft, ask Cambridgeport for a selection corrected for air density. |
| Seismic and wind | IBC seismic and wind-load packages, with certified attachments, stands and anchorage calculations, are engineered per project through the Custom CRAH line. |
| Economizer | Guardian units have no air economizer. Economize on the water side, at the plant. |
| Redundancy | Each frame's fan count is in its tables (sections 1 and 5). N-1 airflow comes with the certified fan selection. |
| Building automation | BACnet/IP native, with dual Ethernet ports. |
Section 12Contacts
For a rating at your own conditions, a selection, a quotation or a submittal, contact Cambridgeport.
Appendix AUnit drawings
Layout, clearances and legend for each frame. Certified drawings are issued with the submittal.